What Size Wire for a 100 Amp Detached Garage 150 Feet Away?
Smallest conductor under 3%
2 AWG
240 volts, single phase, 100 amps, 150 feet one way, 2 AWG copper.
When the figures look right, the circuit material list downloads as a real PDF with your business details on it, built inside your own browser. Nothing you type is uploaded anywhere.
How that number is worked out
These are the figures this page was built with and every line the calculator produces from them. Change anything above and all of it moves.
- System voltage240 V
- PhaseSingle phase
- Load current100 A
- One way run length150 ft
- Conductor size2 AWG
- Conductor materialCopper
Voltage drop2.43% on the run
| Drop | 5.83 V |
|---|---|
| Voltage at the load | 234.2 Vfrom 240 V at the panel |
| Smallest conductor under 3% | 2 AWG |
| Longest run at 2 AWG under 3% | 185 ftone way |
| Conductors to pull | 3including the equipment ground |
The material list this produces
| 2 AWG copper conductor, ft | 495 |
|---|---|
| Conduit or cable, ft | 165 |
| Breaker, 100 A, each | 1 |
| Terminations and lugs, each | 6 |
One way run length compared
Drop is a straight line in length. Double the run and you double the drop, which is why the same wire that is fine in a basement is not fine across a yard.
| One way run length | Voltage drop | Smallest conductor under 3% |
|---|---|---|
| 50 ft | 0.81% on the run | 6 AWG |
| 100 ft | 1.62% on the run | 4 AWG |
| 150 ft | 2.43% on the run | 2 AWG |
| 200 ft | 3.24% on the run | 1 AWG |
| 300 ft | 4.86% on the run | 2/0 |
What else matters here
Two AWG copper gets a 100 amp feeder 150 feet at 2.43 percent.
On a feeder this long the aluminum trade is often worth pricing. Where copper needs 2 AWG, aluminum wants 1/0, and 1/0 aluminum lands at 2.51 percent on this run.
What this calculator assumes
- The formula is the standard one: drop equals 2 times K times amps times the one way length, divided by the circular mil area of the conductor. Three phase uses 1.732 in place of the 2.
- K is 12.9 for copper and 21.2 for aluminum, the usual figures for a conductor running warm in conduit. Circular mil areas come from NEC Chapter 9, Table 8.
- Enter the one way distance, not the loop. The formula doubles it for you, because current has to get back.
- The 3 percent branch circuit and 5 percent total figures in 210.19 and 215 are informational notes rather than requirements. Nobody fails an inspection on voltage drop alone, but motors, LED drivers and long well pump runs care a great deal.
Questions people ask
What size wire do I need for a 100 amp sub panel 150 feet away?
2 AWG copper, or 1/0 aluminum. The 150 foot run pushes 3 AWG copper to 3.06 percent, just past the guideline.
Can I use aluminum instead?
Yes. Aluminum carries about 61 percent of copper's conductivity, so you go up roughly two sizes for the same drop. What matters is the terminations: lugs listed AL or CU-AL, antioxidant compound on the strands, and a torque wrench rather than a feel for it.
The voltage drop calculator takes any dimensions you like and hands back the same list.
Other common sizes
6 more sizes are answered on the voltage drop calculator page