ContractorHandbook

Voltage Drop on a 20 Amp Circuit at 150 Feet

Voltage drop

6.21% on the run

120 volts, single phase, 20 amps, 150 feet one way, 10 AWG copper.

Over 5 percent. This run is too long for the conductor on it. Go up in size, shorten the run, or feed it at a higher voltage, because at this drop motors run hot and equipment warranties start to have opinions.

It does not stop at a number.

When the figures look right, the circuit material list downloads as a real PDF with your business details on it, built inside your own browser. Nothing you type is uploaded anywhere.

panelloadone way length of the run, ftvolts at the far end are lower than volts at the panel3 percent is the limit to design to, and length is what breaks it
Copper is not free of resistance, so voltage arrives smaller than it left, and the loss grows with distance and current. Three percent is the design target, and the fix is nearly always one size bigger conductor rather than a shorter run.

How that number is worked out

These are the figures this page was built with and every line the calculator produces from them. Change anything above and all of it moves.

  • System voltage120 V
  • PhaseSingle phase
  • Load current20 A
  • One way run length150 ft
  • Conductor size10 AWG
  • Conductor materialCopper

Voltage drop6.21% on the run

Over 5 percent. This run is too long for the conductor on it. Go up in size, shorten the run, or feed it at a higher voltage, because at this drop motors run hot and equipment warranties start to have opinions.

Drop7.46 V
Voltage at the load112.5 Vfrom 120 V at the panel
Smallest conductor under 3%6 AWG
Longest run at 10 AWG under 3%72 ftone way
Conductors to pull3including the equipment ground

The material list this produces

10 AWG copper conductor, ft495
Conduit or cable, ft165
Breaker, 20 A, each1
Terminations and lugs, each6

One way run length compared

Drop is a straight line in length. Double the run and you double the drop, which is why the same wire that is fine in a basement is not fine across a yard.

One way run lengthVoltage dropSmallest conductor under 3%
50 ft2.07% on the run10 AWG
100 ft4.14% on the run8 AWG
150 ft6.21% on the run6 AWG
200 ft8.29% on the run4 AWG
300 ft12.43% on the run3 AWG

What else matters here

A hundred and fifty feet at 120 volts is where a 20 amp branch circuit stops being practical in ordinary wire. Even 10 AWG lands at 6.21 percent, and getting under 3 percent needs 6 AWG, which will not terminate on a receptacle at all.

The fix is almost never a bigger branch circuit. It is a sub panel: run a 240 volt feeder to a small panel near the loads and take short branch circuits off it. At 240 volts the percentage drop on the same copper is half, and the branch circuits at the far end are ten feet long instead of a hundred and fifty.

That is the general rule for anything past about 100 feet at 120 volts. Move the panel, do not grow the wire.

What this calculator assumes

  • The formula is the standard one: drop equals 2 times K times amps times the one way length, divided by the circular mil area of the conductor. Three phase uses 1.732 in place of the 2.
  • K is 12.9 for copper and 21.2 for aluminum, the usual figures for a conductor running warm in conduit. Circular mil areas come from NEC Chapter 9, Table 8.
  • Enter the one way distance, not the loop. The formula doubles it for you, because current has to get back.
  • The 3 percent branch circuit and 5 percent total figures in 210.19 and 215 are informational notes rather than requirements. Nobody fails an inspection on voltage drop alone, but motors, LED drivers and long well pump runs care a great deal.

Questions people ask

How far can you run a 20 amp circuit?

At 120 volts and a full load, about 46 feet in 12 AWG and 72 feet in 10 AWG before you pass 3 percent. Past roughly 100 feet the sensible answer is a 240 volt feeder to a sub panel rather than a larger branch circuit.

Why is 240 volts better for a long run?

The same power draws half the current at twice the voltage, and drop is proportional to current. Halve the current and halve the drop, then divide by a voltage that is twice as large, and the percentage drop is a quarter of what it was.

Do I enter the one way run or the total length of wire?

One way, panel to load. The formula multiplies by two for a single phase circuit because the current has to come back, so entering the loop length doubles the answer and sends you two sizes larger than you need.

Different numbers?

The voltage drop calculator takes any dimensions you like and hands back the same list.

Other common sizes