ContractorHandbook

Voltage Drop on 10 AWG at 100 Feet

Voltage drop

4.14% on the run

120 volts, single phase, 20 amps, 100 feet one way, 10 AWG copper.

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

It does not stop at a number.

When the figures look right, the circuit material list downloads as a real PDF with your business details on it, built inside your own browser. Nothing you type is uploaded anywhere.

panelloadone way length of the run, ftvolts at the far end are lower than volts at the panel3 percent is the limit to design to, and length is what breaks it
Copper is not free of resistance, so voltage arrives smaller than it left, and the loss grows with distance and current. Three percent is the design target, and the fix is nearly always one size bigger conductor rather than a shorter run.

How that number is worked out

These are the figures this page was built with and every line the calculator produces from them. Change anything above and all of it moves.

  • System voltage120 V
  • PhaseSingle phase
  • Load current20 A
  • One way run length100 ft
  • Conductor size10 AWG
  • Conductor materialCopper

Voltage drop4.14% on the run

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

Drop4.97 V
Voltage at the load115 Vfrom 120 V at the panel
Smallest conductor under 3%8 AWG
Longest run at 10 AWG under 3%72 ftone way
Conductors to pull3including the equipment ground

The material list this produces

10 AWG copper conductor, ft330
Conduit or cable, ft110
Breaker, 20 A, each1
Terminations and lugs, each6

One way run length compared

Drop is a straight line in length. Double the run and you double the drop, which is why the same wire that is fine in a basement is not fine across a yard.

One way run lengthVoltage dropSmallest conductor under 3%
50 ft2.07% on the run10 AWG
100 ft4.14% on the run8 AWG
150 ft6.21% on the run6 AWG
200 ft8.29% on the run4 AWG
300 ft12.43% on the run3 AWG

What else matters here

Going from 12 to 10 cuts the drop by more than a third, from 6.58 percent to 4.14, because the circular mil area goes from 6,530 to 10,380. That is the general shape of it: one size up is roughly a 37 percent reduction in drop.

Four percent is a common landing place and it is a judgment call. For a receptacle circuit feeding hand tools it is usually accepted. For a circuit running a motor continuously, or LED drivers that flicker below a certain voltage, take it to 8 AWG and be done with it.

The practical difficulty with 10 AWG in a receptacle circuit is the devices. Most 15 and 20 amp receptacles are not rated for a 10 AWG conductor in the back, so the usual approach is to run 10 to a junction box near the load and pigtail down to 12 for the last few feet, where the length no longer matters.

What this calculator assumes

  • The formula is the standard one: drop equals 2 times K times amps times the one way length, divided by the circular mil area of the conductor. Three phase uses 1.732 in place of the 2.
  • K is 12.9 for copper and 21.2 for aluminum, the usual figures for a conductor running warm in conduit. Circular mil areas come from NEC Chapter 9, Table 8.
  • Enter the one way distance, not the loop. The formula doubles it for you, because current has to get back.
  • The 3 percent branch circuit and 5 percent total figures in 210.19 and 215 are informational notes rather than requirements. Nobody fails an inspection on voltage drop alone, but motors, LED drivers and long well pump runs care a great deal.

Questions people ask

Is 4 percent voltage drop acceptable?

It is inside the 5 percent total figure the NEC notes suggest for feeder plus branch circuit, and it is not a code violation in itself. Whether it is acceptable depends on the load: a drill does not care, a well pump motor does.

Can I put 10 AWG wire on a 20 amp breaker?

Yes. The breaker protects the smallest conductor in the circuit, so larger wire on a smaller breaker is always allowed. The reverse is not.

Do I enter the one way run or the total length of wire?

One way, panel to load. The formula multiplies by two for a single phase circuit because the current has to come back, so entering the loop length doubles the answer and sends you two sizes larger than you need.

Different numbers?

The voltage drop calculator takes any dimensions you like and hands back the same list.

Other common sizes