What Size Wire for a 30 Amp RV Outlet 100 Feet Away?

Voltage drop

3.11% on the run

240 volts, single phase, 30 amps, 100 feet one way, 10 AWG copper.

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

It does not stop at a number.

When the figures look right, the circuit material list downloads as a real PDF with your business details on it, built inside your own browser. Nothing you type is uploaded anywhere.

panelloadone way length of the run, ftvolts at the far end are lower than volts at the panel3 percent is the limit to design to, and length is what breaks it
Copper is not free of resistance, so voltage arrives smaller than it left, and the loss grows with distance and current. Three percent is the design target, and the fix is nearly always one size bigger conductor rather than a shorter run.

How that number is worked out

These are the figures this page was built with and every line the calculator produces from them. Change anything above and all of it moves.

  • System voltage240 V
  • PhaseSingle phase
  • Load current30 A
  • One way run length100 ft
  • Conductor size10 AWG
  • Conductor materialCopper

Voltage drop3.11% on the run

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

Drop7.46 V
Voltage at the load232.5 Vfrom 240 V at the panel
Smallest conductor under 3%8 AWG
Longest run at 10 AWG under 3%97 ftone way
Conductors to pull3including the equipment ground

The material list this produces

10 AWG copper conductor, ft330
Conduit or cable, ft110
Breaker, 30 A, each1
Terminations and lugs, each6

One way run length compared

Drop is a straight line in length. Double the run and you double the drop, which is why the same wire that is fine in a basement is not fine across a yard.

One way run lengthVoltage dropSmallest conductor under 3%
50 ft1.55% on the run12 AWG
100 ft3.11% on the run8 AWG
150 ft4.66% on the run8 AWG
200 ft6.21% on the run6 AWG
300 ft9.32% on the run4 AWG

What else matters here

Ten AWG is the correct ampacity for 30 amps and at 100 feet it lands at 3.11 percent, which is just past the guideline. Ten AWG holds 3 percent out to 97 feet on this circuit, so this run misses by three feet.

In practice most people pull 8 AWG for an RV pedestal anyway, and it is the right call. An RV plugged in for a week runs an air conditioner and a water heater on a circuit that is already near its limit, which is exactly the sustained load case where drop matters.

Note the voltage. A 30 amp RV service, the TT-30, is 120 volts, not 240, and at 120 volts this same 10 AWG run drops over 6 percent. If the outlet is a TT-30 rather than a 14-50, switch the voltage above to 120 and size from that number instead.

What this calculator assumes

  • The formula is the standard one: drop equals 2 times K times amps times the one way length, divided by the circular mil area of the conductor. Three phase uses 1.732 in place of the 2.
  • K is 12.9 for copper and 21.2 for aluminum, the usual figures for a conductor running warm in conduit. Circular mil areas come from NEC Chapter 9, Table 8.
  • Enter the one way distance, not the loop. The formula doubles it for you, because current has to get back.
  • The 3 percent branch circuit and 5 percent total figures in 210.19 and 215 are informational notes rather than requirements. Nobody fails an inspection on voltage drop alone, but motors, LED drivers and long well pump runs care a great deal.

Questions people ask

What size wire for a 30 amp RV outlet 100 feet away?

8 AWG copper is the sensible choice. 10 AWG meets the ampacity requirement and lands at 3.11 percent over 100 feet at 240 volts, which is just past the guideline, and considerably worse on a 120 volt TT-30.

Is an RV 30 amp outlet 120 or 240 volts?

A TT-30 is 120 volts on a 30 amp breaker. A 14-50, the one most larger RVs use, is 240 volts at 50 amps. They are not interchangeable and the voltage changes the wire size answer completely.

Is 3 percent voltage drop actually required by code?

No. The 3 percent branch circuit figure and the 5 percent total figure live in informational notes to NEC 210.19 and 215, and informational notes are advisory rather than enforceable. Some jurisdictions adopt them as local amendments and many engineered specs require them, and motors and electronics behave badly on a long undersized run whatever the code says.

Different numbers?

The voltage drop calculator takes any dimensions you like and hands back the same list.