ContractorHandbook

What Size Wire for a Well Pump 300 Feet Away?

Voltage drop

4.94% on the run

240 volts, single phase, 10 amps running, 300 feet one way, 12 AWG copper.

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

It does not stop at a number.

When the figures look right, the circuit material list downloads as a real PDF with your business details on it, built inside your own browser. Nothing you type is uploaded anywhere.

panelloadone way length of the run, ftvolts at the far end are lower than volts at the panel3 percent is the limit to design to, and length is what breaks it
Copper is not free of resistance, so voltage arrives smaller than it left, and the loss grows with distance and current. Three percent is the design target, and the fix is nearly always one size bigger conductor rather than a shorter run.

How that number is worked out

These are the figures this page was built with and every line the calculator produces from them. Change anything above and all of it moves.

  • System voltage240 V
  • PhaseSingle phase
  • Load current10 A
  • One way run length300 ft
  • Conductor size12 AWG
  • Conductor materialCopper

Voltage drop4.94% on the run

Between 3 and 5 percent. Legal, and still worth fixing on a branch circuit that feeds a motor, a heater or a long lighting run. Going up to 8 AWG brings it under 3 percent.

Drop11.85 V
Voltage at the load228.1 Vfrom 240 V at the panel
Smallest conductor under 3%8 AWG
Longest run at 12 AWG under 3%182 ftone way
Conductors to pull3including the equipment ground

The material list this produces

12 AWG copper conductor, ft990
Conduit or cable, ft330
Breaker, 10 A, each1
Terminations and lugs, each6

One way run length compared

Drop is a straight line in length. Double the run and you double the drop, which is why the same wire that is fine in a basement is not fine across a yard.

One way run lengthVoltage dropSmallest conductor under 3%
50 ft0.82% on the run14 AWG
100 ft1.65% on the run14 AWG
150 ft2.47% on the run12 AWG
200 ft3.29% on the run10 AWG
300 ft4.94% on the run8 AWG

What else matters here

Well pumps are the textbook voltage drop failure, and this is why. Ten amps is a small load, 12 AWG looks like plenty of wire for it, and at 300 feet the pump sees 228 volts instead of 240.

A motor at low voltage does not run slower, it draws more current to make the same torque, and the extra current turns into heat in the windings. That shortens the motor's life quietly, over years, and then it fails and gets replaced with an identical motor on the same undersized wire.

The running current is also not the number that hurts. Starting current on a submersible is several times the running figure, and the momentary drop at start is correspondingly larger, which is what stops some pumps starting at all on a long thin run. Size for 3 percent at running load and the starting case takes care of itself. Here that means 8 AWG.

What this calculator assumes

  • The formula is the standard one: drop equals 2 times K times amps times the one way length, divided by the circular mil area of the conductor. Three phase uses 1.732 in place of the 2.
  • K is 12.9 for copper and 21.2 for aluminum, the usual figures for a conductor running warm in conduit. Circular mil areas come from NEC Chapter 9, Table 8.
  • Enter the one way distance, not the loop. The formula doubles it for you, because current has to get back.
  • The 3 percent branch circuit and 5 percent total figures in 210.19 and 215 are informational notes rather than requirements. Nobody fails an inspection on voltage drop alone, but motors, LED drivers and long well pump runs care a great deal.

Questions people ask

What size wire for a well pump 300 feet away?

8 AWG copper for a 10 amp pump at 240 volts, to hold 3 percent. 12 AWG carries the current fine but drops nearly 5 percent over that distance.

Why do well pumps fail from voltage drop?

A motor on low voltage compensates by drawing more current, which heats the windings. It does not fail immediately, it fails early, and the replacement usually goes onto the same wire.

Do I enter the one way run or the total length of wire?

One way, panel to load. The formula multiplies by two for a single phase circuit because the current has to come back, so entering the loop length doubles the answer and sends you two sizes larger than you need.

Different numbers?

The voltage drop calculator takes any dimensions you like and hands back the same list.

Other common sizes